Delta RMC101 User Manual
Page 228
RMC100 and RMCWin User Manual
4-42
• It is already set to 21 ms, which is correct. If the MDT transducer is a clevis-mount type, choose
5 ms.
• Click Update RMC.
• Double-click the Axis 0 Config Word, which opens the following window:
• In the Transducer Type field, select Start/Stop (Rising Edge).
• In the Pressure Axis field, select Aux 2 as the pressure axis. This assigns the pressure axis to
this position axis. This is necessary for the RMC to be able to control position and pressure on
axis 0.
• Leave all the other settings as they are.
• Click OK.
• Issue a Set Parameters (P) command to Axis 0.
6. Scaling the pressure/force axis.
To configure the pressure axis, the following steps are performed:
• Click on any Aux 2 field.
• On the Tools menu, click Scale/Offset Calibration. The following window opens: