between the transducer and the RMC for the interrogation signal, and the '+Ret' and '-Ret'
between the transducer and the RMC for the return signal. Connect the transducer DC ground to
MDT Cmn.
For a single-ended transducer with positive interrogation, connect the transducer '- interrogation
in' wire to the ’r;MDT Cmn’ pin and the transducer '+ interrogation in' wire to the '+ Int' pin.
CONNECT NOTHING TO THE '-Int' PIN OF THE RMC. Connect the transducer return plus wire
to the '+Ret’ pin on the RMC and the transducer return common wire to ’r;MDT Cmn’ on the RMC.
CONNECT NOTHING TO THE '-Ret' PIN OF THE RMC.
Temposonics I transducer users:
For the negative interrogation version of this transducer, connect the transducer '+ interrogation
in' wire to the ’r;MDT Cmn’ pin and the transducer '- interrogation in' wire to the '-Int' pin.
CONNECT NOTHING TO THE '+Int' PIN OF THE RMC. Connect the transducer return plus wire
to the '+Ret’ pin on the RMC and the transducer return common wire to ’r;MDT Cmn’ on the RMC.
CONNECT NOTHING TO THE '-Ret' PIN OF THE RMC.