Delta RMC101 User Manual
Page 349
Ethernet 5.2
Communications
5-99
8. Type a Requested Packet Interval (RPI) between 5.0 and 3200.0 ms in steps of 1.0 ms. The
RMC ignores fractions of a millisecond and cannot support an RPI below 5.0 ms.
9. Set the Inhibit Module and Major Fault On Controller if Connection Fails While in Run Mode
check boxes as required by your application.
10. Click Finish.
The above steps will allocate two or three tags in the Controller Tags database in RSLogix 5000.
These tags correspond to the Input, Output, and Configuration data set up for the module under
the Connection Parameters section above. The type of each tag is a special module-defined type
created by RSLogix. Each special type has a Data field that holds the actual data. The following
table summarizes the tags created for each module:
Tag
Name
Type of
Data
Description
[Name]:I
INT[size]
Input Data.
[Name]:O
INT[size]
Output Data. This tag exists only for Data - INT and
not Input Data - INT connections.
[Name]:C
SINT[400]
Configuration Data. Notice that a full 400 bytes is
allocated by the ControlLogix regardless of how
many are actually configured to be sent to the RMC.
See Controlling the RMC over EtherNet/IP I/O for a description of the contents of the Input,
Output, and Configuration data areas.