beautypg.com

Delta RMC101 User Manual

Page 255

background image

Digital I/O 5.1

Communications

5-5

Figure #5: Open Collector Outputs to RMC CPU Inputs


The RMC’s DI/O inputs are not optimized for use with open collector (sinking) outputs. The
difficulty arises from the fact that sinking outputs have a common ground, but the DI/O also needs
a common ground. Therefore, pullup resisters must be used, as shown in the following diagram
(resister values are described below):

Figure #6: Open Collector Outputs to RMC DI/O Inputs

For 24VDC power, R should be a 3.3kW, ½ watt resister. The output must be capable of
switching 7.5mA when closed. When open collector output is open, the DI/O input sees 7V @
5.1mA.

For 5VDC power, R should be a 560W, 1/8 watt resister. The output must be capable of switching
9.0mA when closed. When open collector output is open, the DI/O input sees 3.1V @ 3.4mA.

Dividing the Input Voltage
Because the inputs are designed for use with 5V outputs, the threshold is 2.75VDC. This is a
small percentage of the 24V outputs. As a result, it is important that the inputs have very little
noise. This section describes using a voltage divider to raise the apparent input threshold.

Note:

Before resorting to dividing the input voltage, take all possible measures to eliminate noise

from the inputs. Also, you may want to employ the software input filters.

This manual is related to the following products: