RMC100 and RMCWin User Manual

6-30

inch. At the desired 0 position, the MDT produces 425 counts.

We first calculate the exact Scale:


With the exact Scale value, we must choose the Prescale Divisor and the rounded Scale value.
The highest divisor value we can use is 1; multiplying the scale by 2, 4, or 8 would all overflow the
Scale limits of ±32767. Therefore we have the following parameters:

Scale = 29879

Prescale Divisor = 1

Next, we must calculate the offset:

Example 2
A system has an MDT with a calibration number of 9.0108 ms per inch and 1 recirculation. The
desired position units are tenths of a millimeter. At the desired 0 position, the MDT produces 1122
counts.

We must first calculate the scale, but in order to do that we need to know how many position units
there are in an inch:

So, we now calculate the exact Scale:


With the exact Scale value, we must choose the Prescale Divisor and the rounded Scale value.
The highest divisor value we can use is 4; multiplying the scale by 8 would overflow the Scale
limits of ±32767. Multiplying the exact scale by this divisor value and rounding gives us the
following parameters:

Scale = 30789

Prescale Divisor = 4

Next, we must calculate the offset:

Example 3
A system has an MDT with a calibration number of 8.9772 ms per inch and 8 recirculations. The
desired position units are thousandths of an inch. Therefore, there are a thousand position units
per inch. At the desired 0 position, the MDT produces 28226 counts.