RMC100 and RMCWin User Manual

5-222

If Compact Mode with Sync is used (versus Compact Mode without Sync), one additional 16-bit
register to hold the Synchronization Output register. See Using the PROFIBUS-DP Compact
Mode for details on using this register and the differences between these two sub-modes.

The order of the output registers for an n-axis module with a Sensor DI/O running in Compact
Mode with Sync is shown below. O represents the RMC’s output base address. If your module
does not have a Sensor DI/O, drop the last two registers:

Register

Number

Contents

O + 0

Synchronization Input

O + 1

Command – axis 0

O + 2

Data out – axis 0

O + 3

Command – axis 1

O + 4

Data out – axis 1

:

:

O + 2*n +

1

Command – axis n

O + 2*n +

2

Data out – axis n

O + 2*n +

3

Reserved by Sensor DI/O

O + 2*n +

4

Reserved by Sensor DI/O


The following chart shows the same for an RMC running in Compact Mode without Sync:

Register

Number

Contents

O + 0

Synchronization Input

O + 1

Command – axis 0

O + 2

Data out – axis 0

O + 3

Command – axis 1

:

:

O + 2*n +

0

Command – axis n

O + 2*n +

Data out – axis n