Delta RMC101 User Manual
Page 457
Modbus Plus 5.3
Communications
5-207
2006
Invalid slave device data area
2007
Invalid slave device network area
2008
Invalid slave device network routing
2009
Route equal to your own address
200A
Attempting to obtain more global data registers
than available
200B
Conflict with Peer Cop (Read Global Data
cannot be used if Peer Cop is used)
30xx
Modbus slave exception response. See error
values 3001-3007 below for specific errors:
3001
Slave device does not support the requested
operation
3002
Nonexistent slave device registers requested
3003
Invalid data value requested
3005
Slave has accepted long-duration program command
3006
Function can’t be performed now—a long-duration
command in effect
3007
Slave rejected long-duration program command
4001
Inconsistent Modbus slave response
5001
Inconsistent network response
6mxx
Routing failure. ’r;m’ indicates the routing entry
at fault (0=Routing 1, 1=Routing 2, etc). See
error values 6m01-6m80 below for specific
errors:
6m01
No response received. For a local node, if m is 0, the
node address was incorrect; check the node address.
If m is 1, the data path was incorrect; ensure that a
data path between 1 and 8 is used. See MSTR Block
Read or MSTR Block Write for details.
6m02
Program access denied
6m03
Node off-line and unable to communicate
6m04
Exception response received
6m05
Router node data paths busy
6m06
Slave device down