beautypg.com

Delta RMC101 User Manual

Page 316

background image

RMC100 and RMCWin User Manual

5-66

Type: This parameter is always set to Peer-To-Peer for Ethernet communication channels.

Read/Write: This parameter should be set to Read to read registers from the RMC, and to Write

to write registers to the RMC.

Target Device: This parameter has possible values of 500CPU, 485CIF, and PLC5. This should

be set to PLC5 for communicating with the RMC.

Local/Remote: This parameter has possible values of Local and Remote. It should be set to

Local for communicating with the RMC.

Control Block: This parameter points to a block of 51 integer-file registers. Set this to a block of

registers, and then use the Setup Screen option in the MSG ladder logic block to modify those
register values:

This Controller: This section holds parameters for the SLC 5/05.

o

Communication Command: This parameter will be set to either PLC5 Read or PLC5

Write. It is not changed from within the Command Block; it is changed in the MSG block
itself.

o

Data Table Address: Enter the address of the first Allen-Bradley PLC register to read RMC

registers into, or to write to RMC registers from.

o

Size in Elements: Enter the number of RMC registers to read or write in this field. The

range enforced by the SLC is 1 to 256 integers. Reads or writes that extend beyond the end
of a register file will continue into the next register file. For example, reading 256 elements
from N9:128 will read N9:128 to N9:255, then N10:0 to N10:127.

o

Channel: Set this to the channel number of the Ethernet channel. For the SLC 5/05, this

should be channel #1.

o

Target Device: This section holds parameters for the target device.

o

Message Timeout: Indicate the number of seconds to wait for the RMC to respond before

determining that the attempt failed. This can be set as low as a few seconds.

o

Data Table Address: Enter the address of the first RMC register to read or write in this

field. See the RMC Register Map (Allen-Bradley) for help on addresses.

o

Ethernet (IP) address: Set this to the IP address of the RMC you wish to communicate

with.

o

MultiHop: This parameter should be set to No.

This manual is related to the following products: