Controller Features

4-51

This example is continued in the next topic.

4.12.5 Position-Pressure Example (Part 3)

This is part 3 of the complete step-by-step example of setting up and tuning a position/pressure
axis.


Part 3: Setting up for Pressure Control

Now that the position control is tuned, the pressure can be tuned. First, the step table must be set
up.

• Set up a step table to simplify entering pressure control. The step table is as follows:

Explanation of the steps:

TIP:

To view the options selected in the Mode word of each Event Step, open the Event Step

table, enter the step exactly as it appears in the figure, and then double-click on the Mode
word for that step.

Step 0:

This step does nothing.

Step 1:

Issues a P command so the axis will hold position. Waits for 1/2 sec so the drive output will
stabilize for the next step.

Step 2:

Issues a Set Null Drive to Integral Drive (n) command. This updates the null drive (the drive
needed to hold position), which is critical for pressure control.