RMC100 and RMCWin User Manual

5-206

The MSTR block indicates it will do an operation using the control block beginning at 400130,
using the one register at 400200. When this block is finished, we look at the third least significant
bit, which represents node 3. If this bit is cleared, then the RMC is disconnected.

The next step is to set up the control block:

Register

Content

400130

9 (decimal): Operation type: Peer Cop Health

400131

0000 (hex): Error status: filled in by function

400132

1 (decimal): Length: we only want one register

400133

0 (decimal): Word Index: we want the first word in
the table

400134-8

0 (decimal): Unused

5.3.7.6 MSTR Block Error Codes

The following list of error codes are returned by the MSTR function block:

Error Code

(Hex)


Meaning

1001

User-initiated abort

2001

Invalid operation type

2002

User parameter changed

2003

Invalid length

2004

Invalid offset

2005

Invalid length + offset