Delta RMC101 User Manual
Page 215
VC2100 and VC2124 Voltage-to-Current Converters 4.11
Controller Features
4-29
VC2100
Fuse the ±15Vdc inputs with 5A maximum, UL-listed, fast-blow fuses. For maximum protection,
use two 500mA fuses per VC2100.
For noise immunity, use twisted, shielded pairs for all connections (twisted pair with overall shield
is acceptable). For best noise immunity, keep wires from the RMC to the VC2100 as short as
possible and less than 98ft (30m), and place ferrites on all cables as close to the VC2124 as
possible. Sample ferrite part numbers from Steward: 28A2029-0A0 or 0A2, 28A5131-0A2,
28A0593-0A2, 28A0807-0A2, 28A3851-0A2, 28A2024-0A0 or 0A2.
Terminal Function
A
+15 volt supply in
B
Power supply common
C
-15 volt supply in
D
Voltage Input 1
E
Common
F
Voltage Input 2
G
Current Output 2