Set parameter on-the-fly, A.1.60 set parameter on-the-fly – Delta RMC101 User Manual
Page 698
RMC100 and RMCWin User Manual
A-46
Why Bother?
These commands are handy when exiting open loop or pressure mode and re-synchronizing
axes. Remember the Target and Actual Positions are the same in these modes. That is why there
is not a relative move from an actual position.
A.1.60 Set Parameter On-the-Fly
Character: None
Decimal: 208-223
Hexadecimal: 0xD0-0xDF
Command Value: Value of the Parameter
Note:
This command is supported in RMC100 CPU firmware dated 19980414 or later.
Each of these commands sets one of the parameters. The following table can be used to
determine which command sets which parameter. Reference axes parameters cannot be set on-
the-fly. Notice that some parameters can never be set on the fly:
Command
MDT, SSI, Quad,
Analog (Position)
Stepper
Pressure/force
Hex
Decimal
Parameter
Parameter
Parameter
0xD0
208
Config. Word
Invalid command
Invalid command
0xD1
209
Scale (2) (4)
Invalid command
Invalid command
0xD2
210
Offset (1)
Coordinate Limit (2)
Invalid command
0xD3
211
Extend Limit (1)
Extend Limit (2)
Invalid command
0xD4
212
Retract Limit (1)
Retract Limit (2)
Invalid command
0xD5
213
Proportional Gain
Compensation Rate (2)
Proportional Gain
0xD6
214
Integral Gain
Compensation Timeout
(2)
Integral Gain
0xD7
215
Differential Gain
Invalid command
Differential Gain
0xD8
216
Extend Feed Fwd.
Steps/Rev (2)
Extend Feed Fwd
0xD9
217
Retract Feed Fwd.
Pos. Units/Rev (2)
Retract Feed Fwd
0xDA
218
Extend Acc. Feed
Fwd.
Quad Counts/Rev (2)
Integrator Preload (
0xDB
219
Retract Acc. Feed
Fwd.
Max. Steps/ms (2)
Filter Time Constan
(3)