Appendix A: Command Reference

A-63

O+3 0000|XXXX|0000|1011 (0X0B)

Issue an Open Loop using Profile 11
command

+4 4000 (0FA0)

Requested Drive

Example for Digital I/O:
Suppose you would like axis 0 to go into open loop at 2000mV of drive using profile 10. You
would send the command in the following format:

Send on Command Strobe going high:

0000|XXXX|0000|1010 (0X0A)

Issue an Open Loop using Profile 10 command

Receive after Acknowledge:

XXXX|XXXX (XX)

Low byte of requested data

Send on Command Strobe going high:

0000|0111|1101|0000 (07D0)

Requested Drive

Receive after Acknowledge:

XXXX|XXXX (XX)

High byte of requested data

A.3.6 Set Parameter Commands

Format: 0AAA RRRR 0001 NNNN

R Used for Status Area Request

N Used for Command Index described below

A Used only by Communication Digital I/O; 0 for PROFIBUS-DP


These commands allow the Programmable Controller to download new initialization parameters
to the RMC. New parameters can be downloaded at any time, but they do not take effect until a
'P' ASCII command is issued. An axis must be stopped when issuing the 'P' ASCII command.

The format of the Command Register for the Set Parameter commands is given below:


1111|11 | |

BIT# 5432|1098|7654|3210

-------------------

HEX |SAR |CMND|INDX

VALUE-------------------

0X10 0AAA|XXXX|0001|0000 Set

CONFIGURATION