beautypg.com

Delta RMC101 User Manual

Page 317

background image

Ethernet 5.2

Communications

5-67


PLC-5 MSG Block Parameters:

The PLC-5 MSG block is displayed as follows:

Control: This parameter points to a block of 51 N-file (integer) registers or two (2) MG-file

(message) registers. Set this to an unused block of registers, and then use the Setup Screen
option in the MSG ladder logic block to modify those register values:

This PLC-5: This section holds parameters for the PLC-5.

o

Communication Command: From this drop-down list, select PLC-5 Typed Read to read

values from the RMC, or PLC-5 Typed Write to write values to the RMC.

o

Data Table Address: Enter the address of the first Allen-Bradley PLC register to read RMC

registers into, or to write to RMC registers from.

o

Size in Elements: Enter the number of RMC registers to read or write in this field. Transfers

are limited to 1000 bytes for PLC-5 Typed Reads and Writes. Therefore, this limit is 500
integers, 250 floats, etc. Notice that this limit is larger than the number of elements in the
RMC's N-files. Reads or writes that extend beyond the end of a register file will continue into
the next register file. For example, reading 300 elements from N9:0 will read N9:0 to
N9:255, then N10:0 to N10:43.

o

Port Number: Set this to the Ethernet channel number. For the PLC-5, this should be

channel #2.

o

Target Device: This section holds parameters for the target device.

o

Data Table Address: Enter the address of the first RMC register to read or write in this

field. See the RMC Register Map (Allen-Bradley) for help on addresses.

o

MultiHop: This parameter should be set to No.

o

Ethernet (IP) address: Set this to the IP address of the RMC you wish to communicate

with.


ControlLogix MSG Block Parameters:

The ControlLogix MSG block is displayed as follows:

This manual is related to the following products: