beautypg.com

Delta RMC101 User Manual

Page 617

background image

SSI 6.6

Transducer Interface Modules

6-73

3 = Gray Code decreasing (24 bits)

6 = Binary increasing (25 bits)

7 = Gray Code increasing (25 bits)

8 = Binary decreasing (25 bits)

9 = Gray Code decreasing (25 bits)

Use the Binary/Gray Code and Data Length fields in the SSI Configuration dialog to match the
code format of the BTL transducer. The increasing/decreasing option indicates whether the
counts increase or decrease away from the head of the transducer. This does not affect the SSI
Configuration dialog, but will need to be taken into account when setting the Scale.


c: System Resolution

1 = 1 µm

2 = 5 µm

3 = 10 µm

4 = 20 µm

5 = 40 µm

7 = 2 µm

This setting does not affect the SSI Configuration dialog, but must be taken into account when
setting the Scale.

Configuring MTS SSI Transducers
MTS’s Temposonics® III family of transducers uses SSI. These transducers may be purchased
with a number of options. These options are indicated by the last seven digits of the part number,
in the format of Sabcdef (e.g. RH-T-0360U-RG0-1-S2B1102), where the lower-case letters each
indicate an option, as described below:

a: Data Length

1 = 25 bits - Set the Data Length field to 25.

2 = 24 bits - Set the Data Length field to 24.


b: Output Format

B = Binary - Select the Binary output-format option.

G = Gray Code - Select the Gray Code output-format option.


c: Resolution

1 = 0.005 mm (5 µm)

This manual is related to the following products: