Delta RMC101 User Manual
Page 423
Ethernet 5.2
Communications
5-173
These registers indicate the current state of the digital inputs and outputs. These registers may
only be read; writes will be ignored, as this product does not support forcing inputs or outputs.
S7 Address
Register Description
DB6.DBW16
CPU Digital Inputs 0 and 1 in LSBs of low
byte, Outputs 0 and 1 in LSBs of high byte
DB6.DBW18
Unused
DB6.DBW20
Unused
DB6.DBW22
Sensor Digital I/O Inputs 0-15
DB6.DBW24
Sensor Digital I/O Inputs 16-17 (stored to two
LSBs)
DB6.DBW26
Sensor Digital I/O Outputs 0-7 in high byte
(low byte unused)
DB6.DBW28
Unused
DB6.DBW30
Unused
Plot Time Registers:
The Plot Time interval is configurable on the RMC. This interval indicates the number of control
loops between each sample in a plot. Therefore, if the control loop is 0.976ms (e.g. RMC100-M1),
this indicates roughly the number of milliseconds between samples. If the control loop is 1.953ms
(e.g. RMC100-M4), this indicates half of the number of milliseconds between samples.
These registers may be read or written. When read, they indicate the plot interval of the currently
gathered plot. When written, they set the plot interval the RMC should use for the next plot it will
gather. When the RMC starts the next plot, it copies the requested plot interval into the currently
used plot interval.
S7 Address
Register Description
DB6.DBW32
Axis 0 plot time interval
DB6.DBW34
Axis 1 plot time interval
DB6.DBW36
Axis 2 plot time interval
DB6.DBW38
Axis 3 plot time interval
DB6.DBW40
Axis 4 plot time interval
DB6.DBW42
Axis 5 plot time interval
DB6.DBW44
Axis 6 plot time interval
DB6.DBW46
Axis 7 plot time interval