C00441 | decoupling analogout, C00442 | aoutx: decoupling value, Carried out in – Lenze 8400 TopLine User Manual
Page 979: C00441, C00442/1, C00442/2, C00442/3, C00442/4, 17 parameter reference
![background image](/manuals/566308/979/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
979
17
Parameter reference
17.2
Parameter list | C00441
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00441
C00442
Parameter | Name:
C00441 | Decoupling AnalogOut
Data type: UNSIGNED_16
Index: 24134
d
= 5E46
h
Configuration defining the events that lead to a decoupling of the analog output terminals.
Configuring exception handling of the output terminals
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF 0x0000 (decimal: 0)
Value is bit-coded: ( = bit set)
Bit 0 SafeTorqueOff
Bit 1 ReadyToSwitchOn
Bit 2 SwitchedOn
Bit 3
Reserved
Bit 4 Trouble
Bit 5 Fault
Bit 6
Reserved
Bit 7
Reserved
Bit 8
Reserved
Bit 9 Fail CAN_Management
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00442 | AOutx: Decoupling value
Data type: INTEGER_16
Index: 24133
d
= 5E45
h
Definition of the value the analog output terminals are to have in the decoupled state.
Configuring exception handling of the output terminals
Setting range
(min. value | unit | max. value)
0.00
%
100.00
Subcodes
Lenze setting
Info
C00442/1
0.00 %
AOut1_U: Decoupling value
C00442/2
0.00 %
AOut2_U: Decoupling value
C00442/3
0.00 %
AOut1_I: Decoupling value
C00442/4
0.00 %
AOut2_I: Decoupling value
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100