C01402 | l_sequencer_1: sequence control: status, C01404 | l_sequencer_1: step for bcancel = true, 17 parameter reference – Lenze 8400 TopLine User Manual
Page 1206
![background image](/manuals/566308/1206/background.png)
17
Parameter reference
17.2
Parameter list | C01402
1206
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01402
C01403
C01404
Parameter | Name:
C01402 | L_Sequencer_1: Sequence control: Status
Data type: UNSIGNED_16
Index: 23173
d
= 5A85
h
From version 12.00.00
0 - READY: Positioning program ready to start/Program end reached.
1 - RUN: Positioning program running.
2 - PAUSE: Current step interrupted, pause active.
3 - BREAK: Positioning program interrupted.
4 - RESET: Positioning program reset.
L_Sequencer_1 (sequence control)
Display range
(min. value | unit | max. value)
0
4
Subcodes
Info
C01402/1
: Sequence control: Status
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01403 | L_Sequencer_1: Sequence control: Control word
Data type: UNSIGNED_16
Index: 23172
d
= 5A84
h
From version 12.00.00
Bit-coded code for controlling the sequencer with a PC or master control via the parameter channel. Setting a bit to
"1" activates the corresponding function:
• Bit 0: Start
• Bit 1: Pause
• Bit 2: Break
• Bit 3: Cancel
• Bit 4: Reset
• Bit 5: NextStep
L_Sequencer_1 (sequence control)
Setting range
(min. value | unit | max. value)
0
64
Subcodes
Lenze setting
Info
C01403/1
0
: Sequence control: Control word
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C01404 | L_Sequencer_1: Step for bCancel = TRUE
Data type: UNSIGNED_16
Index: 23171
d
= 5A83
h
From version 12.00.00
L_Sequencer_1 (sequence control)
Setting range
(min. value | unit | max. value)
0
101
Subcodes
Lenze setting
Info
C01404/1
0
: Step for bCancel = TRUE
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1