Parameter reference
17.2
Parameter list | C00029
894
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00029
C00030
C00033
Parameter | Name:
C00029 | AINx: Input current
Data type: INTEGER_16
Index: 24546
d
= 5FE2
h
Display of the input current at the analog inputs
• When the corresponding analog input is configured for current measurement (
= 1 or 2).
is set = 2 (4 ... 20 mA), 0 ... 16 mA is displayed.
Display range
(min. value | unit | max. value)
0.00
mA
20.00
Subcodes
Info
C00029/1
AIN1: Input current
C00029/2
AIN2: Input current
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C00030 | LS_DFOut: Const.
Data type: INTEGER_16
Index: 24545
d
= 5FE1
h
From version 12.00.00
Settings for the digital frequency output (multi-encoder interface X8)
Setting range
(min. value | unit | max. value)
16
16384
Subcodes
Lenze setting
Info
C00030/1
2048
: number of increments
• The number of increments determines after how
many output increments a zero pulse will be
generated. Each zero pulse defines a covered
"revolution" of the rotary transducer simulated by the
digital frequency output.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00033 | AINx: Output value
Data type: INTEGER_16
Index: 24542
d
= 5FDE
h
Display of the output value in percent of the analog input amplifier
• 100 % ≡ 16384 ≡ +10 V / +20 mA
Display range
(min. value | unit | max. value)
-199.99
%
199.99
Subcodes
Info
C00033/1
AIN1: Output value
C00033/2
AIN2: Output value
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100