C01158
C01190
Parameter | Name:
C01158 | L_SwitchPointPar_1: Invert
Data type: UNSIGNED_16
Index: 23417
d
= 5B79
h
From version 12.00.00
Setting range
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Info
Bit 0 Invert Output1
Bit set = inversion active
Bit 1 Invert Output2
Bit 2 Invert Output3
Bit 3 Invert Output4
Bit 4 Invert Output5
Bit 5 Invert Output6
Bit 6 Invert Output7
Bit 7 Invert Output8
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Subcodes
Lenze setting
Info
C01158/1
0x0000
: Inversion of outputs
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C01190 | Motor thermal sensor
Data type: UNSIGNED_8
Index: 23385
d
= 5B59
h
Selection of the thermal sensor for monitoring the motor temperature
Encoder/feedback system: Motor temperature monitoring (KTY)
Selection list
Info
0 KTY83-110
Lenze standard KTY83-110 (MDSKX, MCS06)
1 Spec. characteristic
Characteristic defined via
2 KTY83-110 + 2 x PTC
Lenze standard KTY83-110 + 2 x PTC 150°C (MCS09-
MCS19)
4 KTY84-130
Lenze standard KTY83-130
Subcodes
Lenze setting
Info
C01190/1
0: KTY83-110
Type of motor temperature sensor resolver
C01190/2
0: KTY83-110
Type of motor temperature sensor MultiEncoder
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1