6 motor phase failure monitoring, Motor phase failure monitoring, 5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 300
5
Motor control (MCTRL)
5.13
Monitoring
300
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.13.6
Motor phase failure monitoring
In order to safely detect the failure of a motor phase, a certain motor current must flow for the
current sensor system. Thus, the response set in
(Lenze setting: "No Reaction") is caused
after a delay time of maximally 2 s after controller enable if a current-carrying motor phase U, V, W
fails or if motor connection is missing. If the current threshold value set in
is already
exceeded within the delay time, the motor phase failure monitoring starts from this point in time.
The monitoring mode checks the current flow for each motor phase as a function of the
commutation angle. Monitoring is activated if a commutation angle of approx. 140° is covered
without the current set in
being exceeded. Monitoring is activated at an output frequency
of 0 Hz if none of the three motor phases reaches the threshold value set in
.
• If the motor phase failure monitoring is tripped:
• The response set in
• The error message "
" is entered into the logbook.
• The bMctrlMotorPhaseFault status output of the
TRUE.
• The motor phase failure monitoring is inactive if
• a controller inhibit is set,
• connection to a rotating machine is carried out (flying restart circuit or connection to actual
speed value),
• an error is pending due to a DC-bus overvoltage ("
"),
• motor parameter identification is carried out,
• DC-injection braking is active.
Note!
In the Lenze setting (
= "0: No Reaction"), the motor phase failure monitoring is
not activated!
In the case of a synchronous motor,
• the motor phase failure monitoring is basically deactivated. (Due to the low no-load
current, the monitoring would be permanently activated.)
• only the
Motor phase error monitoring before operation
is active (for Lenze setting
= "1: Yes").
Note!
If an error response of "1: Fault" is set in
, the bMctrlMotorPhaseFault status
output of the
SB will be set to TRUE for only 1 second in the event of
a motor phase failure because it is no longer possible to detect a motor phase fault via
the error response with a pulse inhibit. However, the Logbook and
still
display the cause of the motor phase failure.