C02867 - identification procedure, C02870 | pli without motion: optimisation factor, C02871 | pli without motion: running time – Lenze 8400 TopLine User Manual
Page 1288: C02867/1, This set, Entification, C02870, C02871, C02873, After ever
17
Parameter reference
17.2
Parameter list | C02867
1288
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C02867
C02870
C02871
Parameter | Name:
C02867 - Identification procedure
Data type: UNSIGNED_8
Index: 21708
d
= 54CC
h
Selection of the identification procedure for motor parameter identification
Automatic motor parameter identification
Selection list
Info
0 automatic
Automatic selection of the optimum identification
procedure:
• For synchronous motors, the extended identification
procedure is always used.
• For asynchronous motors with a rated motor power
of up to 11 kW, the basic identification procedure is
used.
• For asynchronous motors with a rated motor power
of more than 11 kW, the extended identification
procedure is used.
1 standard identification
• Only for asynchronous motors.
• Duration approx. 30 s
2 extended identification
• Stands out due to increased accuracy of the
determined motor parameters.
• Also supports synchronous motors and asynchronous
motors with a power of more than 11 kW.
• Duration approx. 80 s
Subcodes
Lenze setting
Info
C02867/1
0: automatic
Motor parameter identification: Process
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C02870 | PLI without motion: Optimisation factor
Data type: INTEGER_16
Index: 21705
d
= 54C9
h
From version 02.00.00
Pole position identification without motion
Display range
(min. value | unit | max. value)
0.00
%
300.00
Subcodes
Info
C02870/1
PLI without motion: Optimisation factor
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100
Parameter | Name:
C02871 | PLI without motion: Running time
Data type: INTEGER_16
Index: 21704
d
= 54C8
h
From version 02.00.00
Pole position identification without motion
Display range
(min. value | unit | max. value)
0.00
ms
300.00
Subcodes
Info
C02871/1
PLI without motion: Running time
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 100