TA "actuating drive speed (AC Drive Profile)"
482
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.3.5.2
Scaling of speed and torque values
Scaling of the speed values
The speed setpoint is defined by the bus in [rpm]. The conversion then takes place in the controller
as all speed-related signals are processed to a reference variable in percent. An adjustable scaling
factor serves to make an additional scaling.
For the output of the actual speed value to the bus, the following conversion is made:
Scaling of the torque values
The torque setpoint is defined by the bus in [Nm]. The conversion then takes place in the controller
as all torque-related signals are processed to a reference variable in percent. An adjustable scaling
factor serves to make an additional scaling.
For the output of the actual torque value to the bus, the following conversion is made:
Equation for scaling the speed setpoint
Parameter
Name
Description
Appl.: Reference speed
Reference variable for speed-related signals
ACDrive: Speed scaling
In the Lenze setting "0", no scaling takes place (2
0
= 1)
Equation for scaling the actual speed value
Parameter
Name
Description
Appl.: Reference speed
Reference variable for speed-related signals
ACDrive: Speed scaling
In the Lenze setting "0", no scaling takes place (2
0
= 1)
Equation for scaling the torque setpoint
Parameter
Name
Description
Maximum torque
Reference variable for torque-related signals
ACDrive: Torque scaling
In the Lenze setting "0", no scaling takes place (2
0
= 1)
Equation for scaling the actual torque
Parameter
Name
Description
Maximum torque
Reference variable for torque-related signals
ACDrive: Torque scaling
In the Lenze setting "0", no scaling takes place (2
0
= 1)
Speed setpoint
Application
Speed setpoint
Bus
[rpm]
16384
Reference speed [rpm]
----------------------------------------------------------
1
2
Scaling factor
--------------------------------
⋅
⋅
=
Actual speed value
Bus
[rpm]
Actual speed value
Application
Reference speed [rpm]
16384
----------------------------------------------------------
2
Scaling factor
⋅
⋅
=
Torque setpoint
Application
Torque setpoint
Bus
[Nm]
16384 100
⋅
Maximum torque [0.01 Nm]
-------------------------------------------------------------------------
1
2
Scaling factor
--------------------------------
⋅
⋅
=
Actual torque
Bus
[Nm]
Actual torque
Application
Maximum torque [0.01 Nm]
16384 100
⋅
-------------------------------------------------------------------------
2
Scaling factor
⋅
⋅
=