7 can, 8technology applications – Lenze 8400 TopLine User Manual
Page 511
![background image](/manuals/566308/511/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
511
8
Technology applications
8.4
TA "Table positioning"
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
8.4.3.7
CAN
Process data assignment for fieldbus communication
Connection
Assignment
Connection
Assignment
X101/NC-NO
LA_TabPos.bDriveFail
X5/RFR
LA_TabPos.bFailReset
X3/A1U
LA_TabPos.nMainSetValue_a
10 V ≡ 100 % reference speed (
X5/DI1
-
X3/A1I
X5/DI2
-
X3/A2U
-
X5/DI3
LA_TabPos.bLimitSwitchPos
X3/A2I
-
X5/DI4
LA_TabPos.bLimitSwitchNeg
X3/O1U
LA_TabPos.nMotorSpeedAct_a
10 V ≡ 100 % reference speed (
X5/DI5
LA_TabPos.bHomeMark
X3/O1I
X5/DI6
LA_TabPos.bSetQuickstop
X3/O2U
LA_TabPos.nMotorCurrent_a
10V ≡ 100% of I
max_mot
)
X5/DI7
LP_CanOut1: bState_B7
X3/O2I
X107/BD1
LA_TabPos.bMBrakeReleaseOut
X4/DO1
LA_TabPos.bDriveReady
X107/BD2
-
X4/DO2
LA_TabPos.bInTarget
X4/DO3
LA_TabPos.bImaxActive
X107
X4
24B
24O
GB
DO1
BD2
DO3
GO
BD1
DO2
+
M
X5
A2I
AR
COM
A1U
NC
A2U
A1I
NO
X3
DI3
DI2
DI4
DI5
DI6
DI7
GI
24I
DI1
RFR
GA
O1U
O1I
O2U
O2I
X101
24E
+
=
=
+
=
CG
CL
CH
X1
LP_CanIn1
LP_CanOut1
wCtrl
wIn2
wIn3
DriveControl
SpeedOverride
PosProfilePosition
wState
wOut2
wOut3
DriveControlStatus
GPSignalOut1
SetPos
wIn4
wOut4
Speed setpoint
Controller enable
External
supply
24 V DC
pos. direction
neg. direction
Reference switch status
Quickstop
Limit switch
DriveReady
Load mechanicals
in target position
Home position known
Actual speed value (V)
Actual speed value (I)
Act. mot. current val. (V)
Act. mot. current val. (I)
MBrakeReleaseOut