Oh9: motor overtemperature resolver [xx.0119.00003, Oh3: motor temperature (x106) triggered, Error m – Lenze 8400 TopLine User Manual
Page 707: Oh9: motor overtemperature resolver, Oh6: motor temperature multiencoder > c121, Oh12: motor overtemperature multiencoder, Oh9: motor temperature - resolver, Sd6: thermal detector error - resolver, Oh6: motor temperature - multiencoder > c121, Oh12: motor overtemperature - multiencoder
![background image](/manuals/566308/707/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
707
10
Diagnostics & error management
10.9
Error messages of the operating system
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oH9: Motor overtemperature resolver [xx.0119.00003]
Sd6: Error thermal detector resolver [xx.0119.00012]
oH3: Motor temperature (X106) triggered [xx.0119.00015]
oH6: Motor temperature MultiEncoder >= C121 [xx.0119.00020]
oH12: Motor overtemperature MultiEncoder [xx.0119.00021]
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The motor temperature detected via the resolver
interface has reached the fixed limit temperature
(150 °C).
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The signals of the encoder connected to the resolver
interface are outside the defined operating range of the
motor temperature detection.
• Check contacts of the encoder cable at the motor and
controller.
• Check the selected motor temperature sensor in
as to whether it complies with the
assembly in the motor.
• If required, switch off thermal sensor monitoring
(
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The motor temperature monitoring function at the plug
connector X106, terminal T1 /T2, has tripped.
Possible causes:
• The motor is overheated so that the thermal contact
integrated into the motor has been switched.
• An open circuit or a loose contact at the connections
mentioned above has occurred.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The motor temperature detected via the encoder
interface has reached the warning threshold set in
.
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The motor temperature detected via the encoder
interface has reached the fixed limit temperature
(150 °C).
• Check motor temperature monitoring.
• Provide for sufficient cooling of the motor.
• Check terminals for open circuit or loose contact.