Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
273
5
Motor control (MCTRL)
5.10
Parameterisable additional functions
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.10.7.1
Oscillation damping voltage range
The oscillation damping voltage range is successfully used with
• unloaded motors (no-load oscillations)
• motors whose rated power deviates from the rated power of the controller.
• e.g. during operation at high switching frequency including the power derating involved.
• operation with higher-pole motors
• operation with special motors
• compensation of resonance in the drive
• At an output frequency of approx. 20 ... 40 Hz, some asynchronous motors can show
resonance which causes current and speed variations and thus destabilise the running
operation.
How to eliminate speed oscillations in no-load operation at speeds with 40 ... 80 % of the
rated speed:
1. Approach the area where the speed oscillations occur.
2. Reduce the speed oscillations by changing
step by step (increment 1 %).
• The filter time oscillation damping (
) should not be changed.
3. These can be indicators for smooth running:
• Constant motor current characteristic
• Reduction of the mechanical oscillations in the bearing seat
Parameter
Info
Lenze setting
Value Unit
Oscillation damping influence
5.00 %
Oscillation damping filter time
32 ms
Note!
Compensate the resonance during operation with feedback (closed loop, feedback of
n
act
) via the parameters of the slip regulator.
Parameterising the slip regulator