Ps04: par. set mci invalid [xx.0144.00004, Ps07: par. memory module invalid [xx.0144.00007, Ps08: par. device invalid [xx.0144.00008 – Lenze 8400 TopLine User Manual
Page 722: Ps09: par. format invalid [xx.0144.00009, Ps10: memory module binding invalid [xx.0144.00010, Ps10: invalid memory module binding, Error messag, Xx.0144.00004, Xx.0144.00007, Xx.0144.00008
10
Diagnostics & error management
10.9
Error messages of the operating system
722
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
PS04: Par. set Mci invalid [xx.0144.00004]
PS07: Par. memory module invalid [xx.0144.00007]
PS08: Par. device invalid [xx.0144.00008]
PS09: Par. format invalid [xx.0144.00009]
PS10: Memory module binding invalid [xx.0144.00010]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The parameter set saved to the communication module
is incompatible to the standard device.
• An incompatibility of the parameter set is caused e.g.
when the MCI module parameters in the memory
module do not match the plugged communication
module.
When the memory modules are exchanged, observe the
downward compatibility:
• OK: StateLine V2.0 to StateLine V3.0
• OK: StateLine V2.0 to HighLine V2.0
• Not OK: HighLine Vx.x to StateLine Vx.x
• Not OK: StateLine V3.0 to StateLine < V3.0
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The parameter set saved to the memory module is
invalid.
• The error occurs while loading the parameter set.
• The memory module plugged in the device lacks a
code or a code is incorrect.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The parameter set in the device is invalid.
• The error occurs while loading the parameter set.
• One code in the device is incorrect.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The code format is invalid.
• The error occurs while loading the parameter set.
Consultation with Lenze required.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
Device personalisation is active: The binding ID of the
memory module does not comply with the binding ID of
the controller.
• Use memory module/controller with matching
binding IDs.
• Contact machine manufacturer.
Note:
It is not possible for Lenze to modify a replacement
device via special accesses in such a way that it
cooperates with a personalised memory module.