3commissioning – Lenze 8400 TopLine User Manual
Page 67
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
67
3
Commissioning
3.8
Commissioning of the "Table positioning" technology application
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
3.8
Commissioning of the "Table positioning" technology application
[3-2]
Block diagram for wiring the commissioning example for the "Table positioning" application
Note!
Take all the necessary safety precautions before you carry out the following
commissioning steps and switch the device on!
Safety instructions with regard to commissioning
System constellation
X5/RFR
Controller enable
X5/DI1
Position encoder connection, track A
X5/DI2
Position encoder connection, track B
X5/DI3
Hardware limit switch connection in positive direction
X5/DI4
Hardware limit switch connection in negative direction
X5/DI5/DI6 Profile selection and change of operating mode at the same time:
0 | 0 = Profile selection 0 and request for "Speed follower" operating mode
0 | 1 = Profile selection 1 and request for "Homing" operating mode
1 | 0 = Profile selection 2 and request for "Manual jog" operating mode
1 | 1 = Profile selection 3 and request for "Positioning" operating mode
X5/DI7
Start of profile generation
X6
Diagnostic interface for connecting the USB diagnostic adapter
8400 TopLine
X61
X6
DIAG
AR A1U GA
X3
24I RFR DI1 DI2
X5
DI3 DI4 DI5 DI6 DI7
U V W
X6
M
3~
0-Position
20
30
10
-10
-20
-30
40
i
A
B
DI7: PosExecute
DI5/DI6: PosProfile 0 ... 3