Oc2: power section - earth fault [xx.0123.00017, Sd2: open circuit resolver [xx.0123.00024, Sd7: encoder communication error [xx.0123.00026 – Lenze 8400 TopLine User Manual
Page 710: Sd4: open circuit multiencoder [xx.0123.00027, Sd7: error encoder communication, Sd7: encoder communication error, Sd4: open circuit multiencoder, Logbook entry, Sd2: open circuit - resolver, Sd4: open circuit - multiencoder
10
Diagnostics & error management
10.9
Error messages of the operating system
710
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oC2: Power section - earth fault [xx.0123.00017]
Sd2: Open circuit resolver [xx.0123.00024]
Sd7: Encoder communication error [xx.0123.00026]
Sd4: Open circuit MultiEncoder [xx.0123.00027]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised an earth fault at one of the
motor phases. To protect the device electronics, the
inverter control is switched off.
• Mostly, incorrectly executed motor connections are
the cause.
• If motor filter, motor cable length, and cable type
(shielding capacity) are dimensioned incorrectly, this
error message may occur due to leakage currents to
PE.
• If motor filters with additional terminals for +UG and
–UG and devices greater or equal 3 kW are used, the
earth fault detection may be triggered due to leakage
currents to +UG and –UG.
• A cause can also be the use of shielded motor cables
longer than 50 m.
• Check motor connections and the corresponding plug
connector on the device.
• Use motor filters, cable lengths, and cable types
recommended by Lenze.
• If motor filters with additional terminals for +UG and
–UG and devices greater or equal 3 kW are used:
• Deactivate earth-fault detection during operation
by setting the filter time (
) to 250 ms.
• If motor cables longer than 50 m are used:
• Increase filter time for earth-fault detection during
operation (
).
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
• Encoder signal interferences (EMC).
• Resolver cable interrupted.
• Resolver defective.
• Check resolver cable.
• Check resolver.
• Switch off monitoring (
= "0: No reaction")
when the resolver is not used.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
• Encoder cable interrupted.
• Encoder defective.
• Check encoder cable
• Check encoder.
• Check parameter setting.
Response (Lenze setting printed in bold)
Setting:
( Adjustable response)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
• Encoder cable interrupted.
• Encoder defective.
• Supply voltage for the encoder not sufficient.
• Check encoder cable.
• Check encoder.
• Check the set encoder supply voltage in
Adapt setting to the max. permissible encoder supply
voltage. If required, additional voltage drops of the
encoder cable have to be taken into consideration.
• Switch off monitoring (
= "0: No reaction")
when the encoder is not used.