5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 244
![background image](/manuals/566308/244/background.png)
5
Motor control (MCTRL)
5.9
Servo control (SC)
244
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.9.4.4
Setting the current setpoint filter (band-stop filter)
Due to the high dynamic performance/limit frequency of the closed current control loop,
mechanical natural frequencies can be activated which may lead to an unstable speed control loop.
• In the default setting of 0 db of the filter depth (
), the current setpoint filter is switched
off.
Setting of the current setpoint filter
Since the frequency response of the speed controlled system is only rarely known to such an extent
that the current setpoint filter can be adjusted to the controlled system in the run-up, the following
example describes how to set the current setpoint filter.
How to set the current setpoint filter:
1.
.
2.
3. Measure the oscillation frequency (observe current or speed).
4. Set the measured oscillation frequency in
as filter frequency.
5. Set "25%" of the filter frequency in
as filter width.
• Example: Filter frequency = 200 Hz filter width = 50 Hz.
6. Set "40 dB" in
as filter depth.
• If the filter depth is set to "0 dB" (default setting), the filter is not active.
To mask out or at least damp these resonant frequencies, a so-called current
setpoint filter is integrated into the speed control loop of the controller.
Parameter
Info
Lenze setting
Value Unit
SC: Freq. current setpoint filter
200.0 Hz
SC: Current setpoint filter width
0.0 Hz
SC: Current setpoint filter depth
0 dB
Note!
Readjust the speed controller after setting the current setpoint filter.