C00347 | can status heartbeat producer, C00349 | can setting - dip switch, C00349 – Lenze 8400 TopLine User Manual
Page 956: C00347/1...n, 17 parameter reference
17
Parameter reference
17.2
Parameter list | C00347
956
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00347
C00349
Parameter | Name:
C00347 | CAN status HeartBeat producer
Data type: UNSIGNED_8
Index: 24228
d
= 5EA4
h
Selection list
0 Boot-up
4 Stopped
5 Operational
127 Pre-Operat.
250 Failed
255 NoResponse
Subcodes
Info
C00347/1
Status node 1 ... 15
C00347/...
C00347/15
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00349 | CAN setting - DIP switch
Data type: UNSIGNED_16
Index: 24226
d
= 5EA2
h
DIP switch setting during last mains power-on
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Bit 0 Node address 1
Bit 1 Node address 2
Bit 2 Node address 4
Bit 3 Node address 8
Bit 4 Node address 16
Bit 5 Node address 32
Bit 6 Node address 64
Bit 7 Baud rate 1
Bit 8 Baud rate 2
Bit 9 Baud rate 4
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15 DIP switch at 24V-ON accepted
Read access Write access CINH PLC STOP No transfer COM MOT