C00595 | mck: resp. to mck error, C00595/11, C00595/12 – Lenze 8400 TopLine User Manual
Page 1018: Parameterised in, C00595/3, C00595/4, C00595/1, C00595/2, C00595/7, No reaction" dea
17
Parameter reference
17.2
Parameter list | C00595
1018
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00595
Parameter | Name:
C00595 | MCK: Resp. to MCK error
Data type: UNSIGNED_8
Index: 23980
d
= 5DAC
h
Configuration of monitoring of the Motion Control Kernel
Selection list
0 No Reaction
1 Fault
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00595/1
3: TroubleQuickStop
Response if the input bLimitSwitchPos for travel range
monitoring is set to FALSE (fail-safe) by the positive
hardware limit switch .
C00595/2
3: TroubleQuickStop
Response if the input bLimitSwitchNeg for travel range
monitoring is set to FALSE (fail-safe) by the negative
hardware limit switch .
C00595/3
3: TroubleQuickStop
Response for detection that the position is beyond the
positive software limit position (
).
C00595/4
3: TroubleQuickStop
Response for detection that the position is beyond the
negative software limit position (
).
C00595/5
5: Warning
Response if following error limit 1 is exceeded
(
)
C00595/6
5: Warning
Response if following error limit 2 is exceeded
(
)
C00595/7
3: TroubleQuickStop
Response if the maximum travel distance (display in
) is exceeded
C00595/8
4: WarningLocked
Response to start procedures with reference condition
when the reference is not set
C00595/9
4: WarningLocked
Response to a non-supported positioning mode
C00595/10
4: WarningLocked
Response to implausible profile set data
C00595/11
5: Warning
Response to the selection of an invalid operating mode
of the MCK
C00595/12
4: WarningLocked
Response to indicating an invalid profile data set
C00595/13
5: Warning
Response to an error of the FB
C00595/14
4: WarningLocked
Response to a profile start with a target position outside
the software limit positions (
C00595/15
1: Fault
Response to activated connection monitoring in case of
PC manual control
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1