C00644 | pli traversing direction, C00645 | pli max. permissible deflection, C00646 | pli current amplitude – Lenze 8400 TopLine User Manual
Page 1040: C00647 | pli ramp time, C00646/2, C00644/1, C00645/2, C00647/2, C00644/2, The device utilis
17
Parameter reference
17.2
Parameter list | C00644
1040
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00644
C00645
C00646
C00647
Parameter | Name:
C00644 | PLI traversing direction
Data type: UNSIGNED_8
Index: 23931
d
= 5D7B
h
Selection list
0 right rotating field
1 left rotating field
Subcodes
Lenze setting
Info
C00644/1
0: right rotating field
PLI 360° traversing direction
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00645 | PLI max. permissible deflection
Data type: INTEGER_16
Index: 23930
d
= 5D7A
h
Setting range
(min. value | unit | max. value)
-6.0
°
90.0
Subcodes
Lenze setting
Info
C00645/1
0.0 °
Reserved
C00645/2
0.0 °
PLI 360° max. error tolerance
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00646 | PLI current amplitude
Data type: UNSIGNED_16
Index: 23929
d
= 5D79
h
Setting range
(min. value | unit | max. value)
1
%
1000
Subcodes
Lenze setting
Info
C00646/1
1 %
Reserved
C00646/2
100 %
PLI 360° current amplitude
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00647 | PLI ramp time
Data type: UNSIGNED_16
Index: 23928
d
= 5D78
h
Setting range
(min. value | unit | max. value)
5
1000
Subcodes
Lenze setting
Info
C00647/1
5
Reserved
C00647/2
100
PLI 360° ramp time
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1