2 parameter setting, Parameter setting, 12 system bus "can on board – Lenze 8400 TopLine User Manual
Page 799
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
799
12
System bus "CAN on board"
12.10
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.10.2.2 Parameter setting
Short overview of the parameters for the "Heartbeat" monitoring function:
Heartbeat producer time
Time interval for the transmission of the heartbeat telegram to the consumer(s).
• Parameterisable in
or via object
. The parameterised time is rounded down to an
integer multiple of 5 ms.
• The heartbeat telegram is sent automatically as soon as a time > 0 ms is set.
Heartbeat consumer time
Monitoring time for the nodes (producers) to be monitored.
• Parameterisable in
or via object
• The parameterised time is rounded down to an integer multiple of 5 ms and must have a greater
value than the heartbeat producer time of the node to be monitored.
• The maximum number of the nodes to be monitored depends on the device version:
• "BaseLine C": 1 Heartbeat Producer can be monitored.
• "StateLine C": Up to 7 Heartbeat Producers can be monitored.
• "HighLine C": Up to 15 Heartbeat Producers can be monitored.
• "TopLine C": Up to 15 Heartbeat Producers can be monitored.
• The node address(es) of the nodes to be monitored is/are set in
, too.
Heartbeat event
The "Heartbeat event" is activated in the consumer if it does not receive any heartbeat telegram
from the producer within the heartbeat consumer time:
• The consumer changes from the "Operational" communication status to the "Pre-Operational"
communication status.
• The NMT master receives an emergency telegram containing emergency error code 0x8130.
• The response parameterised in
is activated (Lenze setting: "No response").
Parameter
Info
Lenze setting
Assignment
Value Unit
Consumer
Producer
CAN status
of the heartbeat producer 1 ... n
-
Heartbeat producer time
0 ms
CAN node address
of the heartbeat producer 1 ... n
0
Heartbeat consumer time
for the heartbeat producer 1 ... n
0 ms
Resp. to heartbeat event
No response
Highlighted in grey = display parameter