19.1.171.2 Dead time compensation
The delay time of external switching elements can be compensated by setting the corresponding
delay time in
. From this input and the current speed ,the FB calculates a preliminary stop,
i.e. the bOut switching output is set correspondingly earlier.
[19-74] Dead time compensation
19.1.171.3 Switching hysteresis
Setting a hysteresis in
serves to prevent a permanent state change of the bOut switching
output that may be caused by actual position value changes due to a mechanical irregularity at the
axis.
[19-75] Switching hysteresis
Tip!
Please note that a delay time set in
shifts the switching points including the
hysteresis.
Switching performance without dead time compensation
Switching performance with dead time compensation
Switching performance of the external switching element (with dead time)
C01062/1
: Dead time
dnSwitchPoint1_p
dn2ndPoint_Size1_p
bOut1*
bOut1
external component
velocity = nActSpeed_v
t
TRUE
TRUE
"ON"
FALSE
FALSE
"OFF"
0
1
2
CenterMode = FALSE
C01063/1
: Hysteresis
CenterMode = FALSE
CenterMode = TRUE
bOut1
bOut1
dnSwitchPoint1_p
dn2ndPoint_Size1_p
dnSwitchPoint1_p
dn2ndPoint_Size1_p