4 optimising the control mode, Optimising the control mode, 5motor control (mctrl) – Lenze 8400 TopLine User Manual
Page 236
5
Motor control (MCTRL)
5.9
Servo control (SC)
236
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Tip!
Information on the optimisation of the control mode and the adaptation to the real
application is provided in chapter "
Parameterisable additional functions are described correspondingly in the chapter
"
Parameterisable additional functions
5.9.4
Optimising the control mode
The "optimisation steps" given in the table below serve to further optimise the control behaviour of
the servo control and adjust it to the concrete application.
• Detailed information on the individual steps can be found in the following subchapters.
Generally, the following optimisation steps are recommended:
Note!
When the controller has been enabled, starting up is delayed by the magnetization
process of the motor. The speed setpoint is only enabled for motor control if 87 % of the
motor magnetising current are available. If this delay is not tolerable for certain
applications, the preset percentage threshold can be reduced in
.
From version 12.00.00:
• Following successful motor parameter identification, the current controller
parameters (
) and field controller parameters (
calculated automatically.
• If these parameters are not to be calculated, bit 4 of
must be set to "1".
• Following successful motor parameter identification, the speed controller parameters
(
) can be calculated automatically.
• If these parameters are to be calculated, bit 6 of
must be set to "5".
• Following successful motor parameter identification, other controller parameters
(
) can be calculated automatically.
• If these parameters are to be calculated, bit 6 of
must be set to "6".
Optimisation steps
1.
• The current controller should always be optimised if a motor of a third-party manufacturer with
unknown motor data is used!
2.
• The setting of the speed controller must be adapted depending on the mechanical path.
3.
Optimise response to setpoint changes and determine mass inertia
• For an optimal reference behaviour, the total moment of inertia can be used to make a feedforward
control of the speed setpoint.