C00366 | number of can sdo channels, C00367 | can sync rx identifier, T in – Lenze 8400 TopLine User Manual
Page 962: C00366, C00367, Codes, 17 parameter reference
17
Parameter reference
17.2
Parameter list | C00366
962
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00366
C00367
Parameter | Name:
C00366 | Number of CAN SDO channels
Data type: UNSIGNED_8
Index: 24209
d
= 5E91
h
Selection of the number of active parameter data channels
• In the Lenze setting, only the parameter data channel 1 is activated according to CANopen.
• In order to activate both parameter data channels, set the selection "2 SDO Lenze".
Selection list
(Lenze setting printed in bold)
0 1 SDO CANOpen
1 2 SDO Lenze
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00367 | CAN SYNC Rx identifier
Data type: UNSIGNED_16
Index: 24208
d
= 5E90
h
Identifier by means of which the sync slave is to receive sync telegrams.
• Mapping of the CANopen object
(see DS301 V4.02).
Setting range
(min. hex value | max. hex value)
Lenze setting
0x0000
0xFFFF 0x0080 (decimal: 128)
Value is bit-coded: ( = bit set)
Bit 0 COBID Bit0
Bit 1 COBID Bit1
Bit 2 COBID Bit2
Bit 3 COBID Bit3
Bit 4 COBID Bit4
Bit 5 COBID Bit5
Bit 6 COBID Bit6
Bit 7 COBID Bit7
Bit 8 COBID Bit8
Bit 9 COBID Bit9
Bit 10 COBID Bit10
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT