2 parameter setting, Parameter setting, 9basic drive functions (mck) – Lenze 8400 TopLine User Manual
Page 658: Danger
![background image](/manuals/566308/658/background.png)
9
Basic drive functions (MCK)
9.12
Holding brake control
658
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.12.2
Parameter setting
How to go to the parameterisation dialog of the holding brake control:
1. »Engineer« Go to the Project view and select the 8400 TopLine controller.
2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the "Basic functions" button.
4. Go to the Overview Basic functions dialog box and click the Holding brake control button.
Short overview of parameters for holding brake control:
Danger!
A faultless holding brake control function requires a correct setting of the different
deceleration times in the following parameters!
A wrong setting of the delay times can cause a faulty control of the brake!
Parameter
Info
Lenze setting
Value Unit
Holding brake: Operating mode
0: Brake control off
Holding brake: Switching threshold
5.00 %
Holding brake: Hyst. release
1.00 %
Holding brake: Hyst. close
1.00 %
Holding brake: FF control starting value 1
0 %
Holding brake: FF control starting value 2
0 %
Holding brake: Setting
0
Highlighted in grey = display parameter