14 "stand-by" action type, 14 "stand-by" action type 4, L_sequencer_1: "standby" action – Lenze 8400 TopLine User Manual
Page 1664: L_sequencer_1 (sequence control), Standby, Stand-by, Action is active, it is cancell, Action, 19 function library, 1 0 x x x
![background image](/manuals/566308/1664/background.png)
19
Function library
19.1
Function blocks
1664
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
19.1.158.14 "Stand-by" action type
For a temporary activation of a setpoint follower, 5 actions of "stand-by" type are available.
• The corresponding setpoint follower remains enabled until the condition for completing stand-
by is fulfilled.
• If the "stand-by" step is active, the setpoint set in
is provided at the nSet_a output
(Lenze setting: 0 %) .
Action call (entry in the sequence table)
with action number xxx = 001 ... 005
Parameter
The available actions 1 ... 5 are represented via the subcodes 1 ... 5.
Parameter
Possible settings
Info
Stand-by act. n: Input for "End"
• The setpoint follower selected in
remains enabled until
the sequencer input selected here
has the polarity set in
1 Sequencer input 1
(Bit 0 of wDigitalInputs)
2 Sequencer input 2
(Bit 1 of wDigitalInputs)
... ...
16 Sequencer input 16
(Bit 15 of wDigitalInputs)
Stand-by act. n: Polarity input
• State of the selected sequencer
input required for ending the
stand-by an processing the
sequence step.
0 Condition is bit state "0"
1 Condition is bit state "1"
Stand-by act. n: Follower mode
• Selection which follower in the
stand-by mode is to be activated.
0 Operation
-200
%
200 Stand-by act. n: Setpoint
• Setpoint for the
(provided at the output nSet_a).
• Initialisation: 0 %
Standby
1 0 x x x