C00222 | l_pctrl_1: vp, C00223 | l_pctrl_1: tn, C00224 | l_pctrl_1: kd – Lenze 8400 TopLine User Manual
Page 939: C00220, C00221, T in, C00222, In percent, C00223, C00224
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
939
17
Parameter reference
17.2
Parameter list | C00220
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00220
C00221
C00222
C00223
C00224
Parameter | Name:
C00220 | L_NSet_1: Acceleration time - add. setpoint
Data type: UNSIGNED_32
Index: 24355
d
= 5F23
h
FB: Acceleration time for the additional setpoint nNAdd_a
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 0.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00221 | L_NSet_1: Deceleration time - add. setpoint
Data type: UNSIGNED_32
Index: 24354
d
= 5F22
h
FB: Deceleration time for the additional setpoint nNAdd_a
Setting range
(min. value | unit | max. value)
Lenze setting
0.000
s
999.999 0.000 s
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1000
Parameter | Name:
C00222 | L_PCTRL_1: Vp
Data type: INTEGER_16
Index: 24353
d
= 5F21
h
FB: Gain factor Vp for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
500.0 1.0
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10
Parameter | Name:
C00223 | L_PCTRL_1: Tn
Data type: UNSIGNED_16
Index: 24352
d
= 5F20
h
FB: Reset time Tn for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
20
ms
6000 400 ms
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00224 | L_PCTRL_1: Kd
Data type: UNSIGNED_16
Index: 24351
d
= 5F1F
h
FB: Derivative-action coefficient Kd for the PID process controller
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
5.0 0.0
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10