C01251 | mck: acceleration stop, C01251, If th – Lenze 8400 TopLine User Manual
Page 1195: C01251/1, For n, 17 parameter reference
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
1195
17
Parameter reference
17.2
Parameter list | C01251
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C01251
Bit 9 SpeedNormConstant: Up-Limit
1 ≡ Due to the set machine parameters, an internal
calculation constant is limited to a possible maximum.
Remedy: Reduce reference speed in
Bit 10 Max. speed limit
1 ≡ Due to the set machine parameters, the maximum
speed for specifications in [units/s] are limited to the
factor 150 %.
Bit 11 Quick stop is active
1 ≡ Quick stop function is active.
Bit 12 Quick stop standstill is active
1 ≡ Standstill during active quick stop function (no ramp
generation).
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Bit 16
Reserved
Bit 17
Reserved
Bit 18
Reserved
Bit 19
Reserved
Bit 20
Reserved
Bit 21
Reserved
Bit 22
Reserved
Bit 23
Reserved
Bit 24
Reserved
Bit 25
Reserved
Bit 26
Reserved
Bit 27
Reserved
Bit 28
Reserved
Bit 29
Reserved
Bit 30
Reserved
Bit 31
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C01247 | MCK: Diagnostic word
Data type: UNSIGNED_32
Index: 23328
d
= 5B20
h
Parameter | Name:
C01251 | MCK: Acceleration stop
Data type: INTEGER_32
Index: 23324
d
= 5B1C
h
Acceleration parameter for stop
Setting range
(min. value | unit | max. value)
-214748.3647
units/s2
214748.3647
Subcodes
Lenze setting
Info
C01251/1
720.0000 units/s2
MCK: Stop: Decel.
• Deceleration for setpoint speed ramp-down to
standstill.
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 10000