_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00159
C00160
Parameter | Name:
C00159 | Cause of quick stop QSP
Data type: UNSIGNED_16
Index: 24416
d
= 5F60
h
Bit coded display of the cause/source of the quick stop
Display area
(min. hex value | max. hex value)
0x0000
0xFFFF
Value is bit-coded:
Bit 0
Reserved
Bit 1 CAN control word
Bit 2 MCI control word
Bit 3
Reserved
Bit 4 Application
Bit 5 Device command
Bit 6 Error response
Bit 7 Internal signal
Bit 8
Reserved
Bit 9
Reserved
Bit 10 Operating system
Bit 11
Reserved
Bit 12 MCK
Bit 13
Reserved
Bit 14
Reserved
Bit 15
Reserved
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00160 | Status determining error (16bit)
Data type: UNSIGNED_16
Index: 24415
d
= 5F5F
h
Display of the short 16-bit error number of the status determining error
Structure of the 16-bit error number (bit coding)
Display range
(min. value | unit | max. value)
0
65535
Subcodes
Info
C00160/1
Status determining error (16-bit)
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1