5 monitoring of the rpdos for data reception, 6 configuring exception handling of the can pdos, Monitoring of the rpdos for data reception – Lenze 8400 TopLine User Manual
Page 783: Configuring exception handling of the can pdos, 12 system bus "can on board
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
783
12
System bus "CAN on board"
12.8
Process data transfer
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.8.5
Monitoring of the RPDOs for data reception
For RPDO1 ... RPDO4 each, a monitoring time can be parameterised within which the RPDO must
arrive. If the RPDO is not received within the monitoring time or not with the configured sync, the
response parameterised for each RPDO takes place.
Short overview: Parameters for RPDO monitoring
12.8.6
Configuring exception handling of the CAN PDOs
Exception handling for the CAN PDOs in the event of an error can be set via decoupling
configuration and decoupling values.
• Bit coded selection is carried out in
for the process data words read by the bus,
defining the events that will trigger decoupling.
• Bit coded selection is carried out in
for the process data words output by the
application, defining the events that will trigger decoupling.
Parameter
Info
Lenze setting
Value Unit
CAN1...4_IN monitoring time
3000 ms
Resp. to CAN1...4_IN monitoring
No response
Bit
Event
Bit 0 BusOff_MsgErr
Bit 1 Warning
Bit 2 NodeStopped
Bit 3 HeartBeatEvent
Bit 4 CAN1_In_Überw.
Bit 5 CAN2_In_Überw.
Bit 6 CAN3_In_Überw.
Bit 7 CAN4_In_Überw.
Bit 8
Reserved
Bit 9
Reserved
Bit 10
Reserved
Bit 11
Reserved
Bit 12
Reserved
Bit 13
Reserved
Bit 14 Trouble
Bit 15 Fault