Os2: max. motor speed [xx.0123.00033, Id3: cinh identification [xx.0123.00058, Id4: resistor identification error [xx.0123.00059 – Lenze 8400 TopLine User Manual
Page 712: Os2: max. motor speed reached, Xx.0123.00057, Xx.0123.00056, Xx.0123.00058, Xx.0123.00059, Xx.0123.00033, 10 diagnostics & error management
10
Diagnostics & error management
10.9
Error messages of the operating system
712
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
oS2: Max. motor speed [xx.0123.00033]
Id2: Motor data identification error [xx.0123.00056]
Id1: Motor data identification error [xx.0123.00057]
Id3: CINH identification [xx.0123.00058]
Id4: Resistor identification error [xx.0123.00059]
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that the maximally
permissible motor speed has been reached.
• Limit setpoint selection to the maximally permissible
motor speed.
• If required, adapt set maximum motor speed
(
).
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
During the identification of the motor parameters, an
error has occurred that caused an abortion of the
identification process.
Possible causes:
• Interrupted motor cable.
• Switched-off power section during the identification.
• Implausible start parameter settings.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Correct start parameters for the motor parameter
identification (motor nameplate data).
• Stable power supply of the device.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
During the identification of motor parameters, an error
has occurred.
Possible causes:
• Interrupted motor cable.
• Switched-off power section during the identification.
• Implausible start parameter settings.
• Check the motor connections and the corresponding
plug connector on the device and, if necessary, the
motor terminal box.
• Correct start parameters for the motor parameter
identification (motor nameplate data).
• Stable power supply of the device.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has detected controller inhibit during the
motor data identification.
• This cancels the identification process. The Lenze
setting of the motor data is used.
• Do not set controller inhibit during the motor data
identification.
• Do not execute any device function which may
activate controller inhibit.
Response (Lenze setting printed in bold)
0: No Reaction 1: Fault 2: Trouble 3: TroubleQuickStop 4: WarningLocked 5: Warning 6: Information
Cause
Remedy
The device has recognised that an error has occurred in
the calculation of the motor cable resistance.
• The parameters for cable cross-section and cable
length are implausible.
Enter sensible values for cable cross-section and motor
cable length.