8 mains phase failure monitoring, 9 maximum current monitoring, Mains phase failure monitoring – Lenze 8400 TopLine User Manual
Page 303: Maximum current monitoring, Ation, 5motor control (mctrl)
![background image](/manuals/566308/303/background.png)
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
303
5
Motor control (MCTRL)
5.13
Monitoring
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.13.8
Mains phase failure monitoring
The drive controller has a simple mains-phase failure detection function with which a mains phase
failure can be detected under load.
• In the case of power-adapted machines, approx. 50 % of the rated motor power must be
exceeded so that a main-phase failure can be detected.
• If the mains phase failure monitoring is tripped:
• The error response set in
will be carried out (Lenze setting: "Warning").
• The "
Su02: One mains phase is missing
" error message will be entered into the logbook.
• The bMctrlMainsFault status output of the
system block will be set to
TRUE.
5.13.9
Maximum current monitoring
If the parameterised maximum current is reached, the response set in
is triggered (Lenze
setting: "0: No Reaction").
If the activated monitoring is tripped:
• The "
" error message is entered in the logbook.
Related topics:
Stop!
Under load, the mains input of a three-phase controller can be destroyed if the device is
only supplied by two phases (e.g. if a mains phase fails).
Note!
In the Lenze setting (
= "0: No Reaction"), the maximum current monitoring is not
activated!
If a Lenze motor is selected from the catalogue whose plant parameters are transferred
into the controller, the setting of the maximum current in
and
automatically be adapted to the selected motor.