Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.3.2.6
Configuration example 2: Distance sensor "DME5000-117" by SICK
Data
from DME5000 operating instructions (8009813/US35/2012-07-02):
• Maximum distance: 70 m
• Default setting of parameter "Period Length": 1 mm
(4 zero crossings while passing one period * 0.25 mm = 1 mm)
• Default setting of parameter "Resolution": 125 μm (must not be changed)
These default settings result in the following resolutions:
• 1 "encoder revolution" = 10 mm
• Hiperface resolution: 1/32 mm 320 digits per "revolution" x 7000 "revolutions"
• Sin/cos resolution: 10 increments per "revolution"
(1 period ≡ 1 mm 10 mm ≡ one "revolution" = 10 periods or increments)
• 1 [unit] = 1 mm
Scaling of the position value
In order to scale the evaluation of the SinCos track, the traverse path in [units] has to be entered in
which is covered in order to pass through once the SinCos increment of the encoder
(
) (here 10 increments x 1 mm period length = 10 mm).
The absolute Hiperface track is scaled by the setting of the "steps per revolution" in
. Here,
a revolution is equated to the path which corresponds to the SinCos number of increments of the
encoder (
).
Required settings
Period Length (mm)
Type code
Resolution RS-485 (mm)
Resolution sin/cos when zero crossings are counted (mm)
1
90h
1/32
0.25
2
91h
1/16
0.5
4
92h
1/8
1
8
93h
1/4
2
16
94h
1/2
4
Parameter
Info
Setting for example
Hiperface: Number of revolutions
7000
Hiperface: Steps per revolution
320
LS_MultiEncoder: Solid measure
1: linearly unipolar
LS_MultiEncoder: Encoder increment
10
LS_MultiEncoder: Traverse path - encoder increment
10