3commissioning – Lenze 8400 TopLine User Manual
Page 91
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
91
3
Commissioning
3.10
PC manual control
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
How to activate the PC manual control:
1. If an online connection to the controller has not been established yet:
Go online.
2. Select the Application parameters tab from the Workspace.
3. Go to the Overview dialog level and click the PC manual control button.
• First, the following safety note is displayed:
• Click the Cancel button to abort the action and close the dialog box.
• The Timeout monitoring input field serves to adapt the timeout for monitoring the
connection between the PC and the controller.
4. To acknowledge the note and activate PC manual control:
Click the Connect PC manual control button.
• The controller is inhibited via device command (
).
• The PC manual control operator dialog is displayed.
Note!
With active PC manual control:
The online connection between PC and controller is monitored by the controller.
• If the online connection is interrupted longer than the timeout time set (Lenze
setting: 2 s):
• The error response "Fault" takes place, i.e. the motor becomes torqueless and
coasts, if it has not yet been in standstill.
• The "
Ck16: Time overflow manual control
" error message is entered into the
logbook.
PC manual control provides the Motion Control Kernel and the motor interface with all
required control signals and setpoint signals.
• The available application (function block interconnection) is now decoupled from
these interfaces, but is continued to be processed and remains unchanged.
• It does not matter what type of motor control is set in
.