Scaling factor
The "scaling factor" is important for parameter access via a bus system.
Example 1: The value "654" of the parameter
(AIN1: input voltage) read via a bus system
must be divided by the corresponding scaling factor "100" to obtain the actual display value
"6.54 V".
[17-1] Conversion formula for read access via bus system
Example 2: In order to set the parameter
(acceleration time main setpoint) to the value
"123.45 %" via a bus system, the integer value "12345" must be transferred, i.e. the value to be set
must be multiplied by the corresponding scaling factor "100".
[17-2] Conversion formula for write access via bus system
Character length
In case of parameters of "VISIBLE_STRING" data type, the character length is given in addition. This
is also important for the parameter access via a bus system.
Signal type
Scaling factor
Resolution
Value range
Analog (scaled)
100
16 bits signed
± 199.99 %
Angular velocity
1
16 bits signed
± 32767 incr./ms
Position in [units]
10000
32 bits signed
± 214748.3647 [units]
Digital (BOOL)
1
8 bits unsigned
0 ≡ FALSE; 1 ≡ TRUE
Time
1000
16 bits unsigned
0 ... 999.000 s
Selection value
1
16 bits unsigned
0 ... 65535
Read value (via bus system)
Scaling factor
-----------------------------------------------------------------------
Indicated value (Engineer)
=
Value to be written (via bus system)
Value to be set Scaling factor
⋅
=