6encoder/feedback system – Lenze 8400 TopLine User Manual
Page 320
6
Encoder/feedback system
6.2
Resolver (X7)
320
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameterisation dialog (cutout)
How to parameterise the resolver:
1. If number of resolver pole pairs ≠ 1:
Set number of pole pairs (
).
2. Select resolver as speed sensor (
) or/and as position encoder (
3. Adjust filter time of the actual speed value (
) if necessary.
• Lenze setting: 2 ms
• Lenze recommend a filter time between 1 ... 2 ms.
4. If you use the resolver as motor encoder and the servo control with synchronous motor of
a original equipment manufacturer: Carry out
Pole position identification (PPI)
5. For detecting and monitoring the motor temperature via the resolver cable:
Motor temperature monitoring (KTY) via resolver
.
Resolver/multi-encoder open-circuit monitoring
.
In the Lenze setting, the resolver cable and/or encoder cable are monitored with regard to
open circuit as a function of the selected speed and position encoder.
7. For a permanent acceptance of the parameter settings:
Save parameter set.
Parameter
Info
Lenze setting
Value Unit
LS_Resolver: Number of pole pairs
1
LS_Resolver: Encoder filter time
2.0 ms
Activate resolver error comp.
0: Activate resolver error
compensation
Resolver: cos gain
100.00 %
Resolver: sine gain
100.00 %
Resolver: Phase error
0.00 %