C00588 | resp. to max. speed at switching freq, C00590 | resp. to switching frequency red, C00591 | resp. to axis bus error – Lenze 8400 TopLine User Manual
Page 1015: C00591/1, C00591/2, C00590, C00588, Is activat, 17 parameter reference
Lenze · 8400 TopLine · Reference manual · DMS 6.0 EN · 06/2014 · TD05/TD14
1015
17
Parameter reference
17.2
Parameter list | C00588
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00588
C00590
C00591
Parameter | Name:
C00588 | Resp. to max. speed at switching freq.
Data type: UNSIGNED_8
Index: 23987
d
= 5DB3
h
Response if the maximum speed for the set inverter switching frequency is reached (
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00590 | Resp. to switching frequency red.
Data type: UNSIGNED_8
Index: 23985
d
= 5DB1
h
Response to reduction of the inverter switching frequency (
Selection list
(Lenze setting printed in bold)
0 No Reaction
1 Fault
5 Warning
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1
Parameter | Name:
C00591 | Resp. to axis bus error
Data type: UNSIGNED_8
Index: 23984
d
= 5DB0
h
From version 12.00.00
Configuration of axis bus monitoring
Selection list
0 No Reaction
1 Fault
2 Trouble
3 TroubleQuickStop
4 WarningLocked
5 Warning
6 Information
Subcodes
Lenze setting
Info
C00591/1
0: No Reaction
Resp. to axis bus data error
C00591/2
0: No Reaction
Resp. to axis bus IO error
Read access Write access CINH PLC STOP No transfer COM MOT
Scaling factor: 1